6-channel power relay module

revision 112495
Covered order codes (1)
  • WB-MRPS6/S


This page describes the latest hardware revision with the latest stable firmware. If your device runs older firmware, update it where possible (see Firmware update).
MRPS6 module
MRPS6 module
MRPS6 PCB
MRPS6 PCB

Purpose

WB-MRPS6 six-channel relay modules switch general-purpose power loads, including inductive and capacitive loads: LED luminaires, incandescent lamps, switching power supplies, PDU applications and similar equipment.

The modules support a maximum current of 16 A (10 A nominal load) and can be used without intermediate contactors.

Not suitable for switching three-phase loads under the cited requirements, because the contacts must be mechanically interlocked for that application (GOST 30011.4.1, clause 7.2.1.1.5).

For relay selection, see Relay selection recommendations.

Technical specifications

Parameter Value
Power supply
Supply voltage 9–28 V DC
Power consumption
  • all relays off — 0.5 W;
  • all relays on — 3 W;
  • peak — up to 8 W for 20 ms.
Outputs
Number of outputs 6
Output type Mechanical relay contacts
Contact configuration Two-position, normally open (COM and NO)
Output arrangement 6 outputs connected to relay contacts
Maximum switching voltage, AC 250 V
Maximum switching voltage, DC 30 V
Rated switching current per output at 230 V AC 10 A
Maximum switching current per output at 230 V AC 16 A
Maximum switching current per output, DC 16 A at 24 V; 10 A at 30 V (resistive load, room temperature, service life of 20,000–50,000 switching operations)
Maximum inrush current (20 ms) at 230 V AC 165 A
Contact resistance < 100 mΩ
Contact material W+AgSnO2
Dielectric withstand voltage between relay coil and contacts 5000 VAC (1 minute)
Dielectric withstand voltage between open relay contacts 1250 VAC (1 minute)
Operating life 12,000 operations at 16 A / 230 VAC
Detailed specifications HF115F-S
Datasheet HF115F-S.pdf
Inputs
None
Delays
Startup Delay When Power On (s) 0–999 s; default: 0 s
Restart Delay After Output Turn Off (s) 0–999 s; default: 0 s
Indicators
LED See Indicators
Control
Control interface RS-485
Interface isolation Non-isolated
Communication protocol Modbus RTU; software-configurable address; factory settings are printed on the label
RS-485 interface parameters Software-configurable; defaults:

baud rate — 9600 bit/s; data — 8 bits; parity — none (N); stop bits — 2

Ready after power-on ~2 s
Operating conditions
Ambient air temperature −40 to +80 °C
Relative humidity Up to 95%, non-condensing
Climatic classification under GOST 15150-69 O2.1*
Warranty 2 years
Service life 8 years
Terminal blocks and wire cross-sections
Recommended wire cross-section with insulated wire-end ferrules control inputs: 0.35–1 mm2 — single ferrule; 0.35–0.5 mm2 — twin ferrule,

power inputs: up to 2.5 mm2 — single ferrule; up to 1.5 mm2 — twin ferrule

Standard ferrule sleeve length 8 mm
Screw tightening torque control inputs: 0.2 N·m,

power outputs: 0.5 N·m

Dimensions
Width, DIN modules 3
Overall dimensions (L × W × H) 53 × 90 × 58 mm
Weight (including box) 195 g

Operating principle

Indicators

WB-MRPS6 indicators
WB-MRPS6 indicators

The module has indicators that show its status without connecting to a controller:

  • S (green) — Modbus communication status: lights up when low-voltage power is applied and flashes during polling over RS-485. On devices with events enabled in Fast Modbus ⚡ the indicator flashes more frequently than during sequential polling because events are polled faster. In bootloader mode it flashes once per second; during firmware upload it flashes rapidly.
  • 1–6 (orange) — output state: lit when the relay contacts are closed.

Inputs

There are NO digital inputs.

Outputs

The module has six independent normally open relay outputs. The permissible current for DC loads is specified in the technical specifications. For permissible load power and type, see Relay selection recommendations.

Safety Mode

Safety Mode can stop a process if control over the module is lost, for example if the RS-485 cable is severed. Account for loss of controller communication when designing control systems (see Configuring Safety Mode)

Actuator Control

Roller blind motor
Roller blind motor
Curtain track motor
Curtain track motor

Despite the wide range of actuators with digital control, mains-switched actuators remain common for curtains, blinds, shutters, projector screens, air dampers, ball valves and similar devices. Their main control requirement is to prevent simultaneous activation of Open and Close.

The module's Actuator Control combines two relays into one control and uses a software interlock to prevent both relays being energised simultaneously. It also inserts a 500 ms delay when reversing direction and energises the relays for the configured duration (10 seconds by default).

For actuator safety, relay coil commands are ignored in this mode. These outputs can be controlled only through Actuator Control registers.

Actuator Control is disabled by default. Enable it in the settings before use; delays are configured there too.

Delays

Startup Delay When Power On (s) starts when the device firmware boots, approximately 2.5 s after low-voltage power is applied. It switches outputs on sequentially to protect supply circuits from combined inrush currents.

Restart Delay After Output Turn Off (s) starts when the relay switches off. It protects loads sensitive to frequent switching, such as compressors and pumps.

Delays are configured separately for each relay output.

Output timer functions

Timer functions switch module outputs on or off according to a defined timing sequence.

Direct control and timer functions can be used in the same module. Each output can have only one timer function. Outputs are configured independently; changing one output does not affect the others. More about relay module timer functions.

Each relay output supports these timer functions: On Delay, Off Delay, Switch on for a time, Switch on for a time (with command reset), Switch off for a time, Switch off for a time (with command reset), On/Off Cycle.

Configuring output timers.

Installation

Mount the device on a standard 35 mm DIN rail. The V+ GND A B terminal block, with a 3.5 mm pitch, connects the power supply and RS-485 communication bus. Correct bus wiring is essential for reliable communication; see RS-485 bus wiring and connection.

If devices on the RS-485 bus use different power supplies, their GND terminals must be interconnected. See Grounding Wiren Board devices and connecting GND and iGND.

Crimping insulated wire-end ferrules
Crimping insulated wire-end ferrules

Use flexible stranded wire with insulated wire-end ferrules (NSHVI).

Strip the insulation to the sleeve length, or strip a little more and trim the protruding wire after crimping. Use a ferrule crimping tool. A crimped ferrule protects the strands from the screw clamp and secures the connection.

Do not overtighten the terminal screws: excessive force damages the screw terminal.

Relay switching briefly increases power consumption (see specifications). Choose a supply with adequate power reserve. For long supply cables, allow for the voltage drop along the cable.

The conductor cross-section at the relay output screw terminals must suit the switched load. The screw terminals accept 2.5–4 mm2. Install the relay module to meet electrical safety requirements and prevent accidental contact with live high-voltage terminals. Operate the device under the recommended environmental conditions.

Installation example

WB-MRPS6 installation example
WB-MRPS6 installation example

One way to connect loads to WB-MRPS6 is shown in the diagram WB-MRPS6 installation example.

In this example, wiring before and after the relay is protected by a 10 A circuit breaker. Select its rating for the installed conductor size and the module's maximum switching current.

The diagram connects a water heater, a fan, an LED lamp and an incandescent lamp to K1–K4. Outputs are controlled over RS-485.

Connecting curtain actuators

Curtain actuator connection example for WB-MRPS6
Curtain actuator connection example for WB-MRPS6

Before connecting a curtain actuator, enable Actuator Control for the outputs used! Incorrect configuration can energise both relays simultaneously and may damage some actuators.

A curtain actuator uses two relays, typically connected to mains phase L and the actuator's Open and Close wires. The actuator is also connected to neutral N and protective earth PE. Always check the proposed wiring against the actuator documentation.

Up to three curtain actuators can be connected to one WB-MRPS6.

Available output functions
Actuator Outputs
1 K1 - open, K2 - close
2 K3 - open, K4 - close
3 K5 - open, K6 - close

Configuration

Configuration methods

  1. Set the parameters in the Wiren Board controller web interface under Settings → Configs → Serial devices driver configuration. If these items are unavailable, check your access level.
  2. Write settings to the Modbus registers of the module from the controller console using the utility modbus-utils-rpc or modbus­_client.
  3. Without a Wiren Board controller, use the Wiren Board device web configurator or other software; see Using Wiren Board Modbus devices without a controller. You will need a computer with an interface converter: USB-RS485.

Our devices are continually improved. If settings described in this manual are missing, update the device firmware and controller software.

Output states at power-on

Configuring relay states at power-on
Configuring relay states at power-on

The following power-on behaviours are available:

  • Safe state (default) — after power-on, outputs follow the setting Output Safe State;
  • Restore last state — saves the last output state and restores it when power returns.

Safety Mode

Fail-safe settings
Fail-safe settings

Safety Mode can stop a process if control of the module is lost, for example because the RS-485 cable is severed. Account for communication loss when designing control systems.

The fail-safe timer restarts after every successfully received and processed Modbus packet. The module enters safe mode when the configured time expires. Normal operation resumes when communication returns. The default timeout is 10 seconds.

Each output has a configurable fail-safe state and can be configured to enter it on communication loss.

Input control behaviour can be configured:

  • Don't change — previously enabled input control remains enabled.
  • Block in safe mode — inputs cannot control the relays.
  • Allow only in safe mode — input control blocked in normal operation becomes available in safe mode.

Actuator Control

Configuring actuator control for K1 and K2
Configuring actuator control for K1 and K2

To use an actuator, select the corresponding output mode on the Actuator Control tab. Opening/closing times, direction-change pause, power-on actions and safe-mode actions then become available.

Outputs in one module can use different modes: for example, K1 and K2 can control an actuator while K3–K6 operate normally.


Configuring protective delays

In the device settings, open Protective Functions and set the Startup Delay When Power On (s) or Restart Delay After Output Turn Off (s) for the corresponding relay output.

Configuring output timers

In the device settings, open Timers, select a function and configure its duration for the corresponding relay output.

Wiren Board controller web interface

Selecting a template

To display the device on the Devices tab of the Wiren Board controller web interface, add it automatically by scanning for Wiren Board devices on RS-485 or manually by selecting the template WB-MR6CU v.2, WB-MRPS6.

Controlling the device and viewing values

The web interface allows you to control device outputs and view readings. To change the displayed channels, edit the device configuration in the wb-mqtt-serial driver settings.

Modbus operation

Wiren Board devices use Modbus RTU. The physical connection uses the RS-485.

interface. All main commands for reading and writing one or multiple registers are supported. See the list in the Modbus protocol description.

The module can be configured:

Default port settings

Value
default
Parameter name
in the web interface
Parameter
9600 Baud rate Baud rate, bit/s
8 Data bits Number of data bits
None Parity Parity
2 Stop bits Number of stop bits

In current firmware, setting Stop bits is optional: the device also operates correctly when its number of stop bits differs from the Modbus master setting.

For a faster response, we recommend increasing the baud rate to 115200 bit/s; see Communication parameter settings

Modbus address

Factory-assigned Modbus address. Left: label on the device cover. Right: label on the side or underside of the device.
Factory-assigned Modbus address. Left: label on the device cover. Right: label on the side or underside of the device.

Each device on the bus must have a unique address from 1 to 247. The factory-assigned address is printed on labels on the enclosure (top cover, side or underside). Devices in a production batch are assigned different addresses, so devices in one order will usually have different addresses.

For instructions on finding, changing or resetting the address, see Wiren Board device Modbus address.

Fast Modbus extension

Fast Modbus extends standard Modbus with rapid discovery of Wiren Board devices on RS-485 and event polling.

These features are enabled by a special command from the master, so Wiren Board devices remain compatible with third-party equipment.

Not every register supports event generation. Check the register map: event-capable registers are marked with ⚡. See Fast Modbus.

Register map

Relay module register map

Firmware updates and resetting settings

Wiren Board devices support firmware updates over Modbus. This allows bugs to be fixed at the installation site and, where technically possible, new features to be added. Settings stored in the device are retained during a firmware update.

Instructions:

New firmware releases are listed in the firmware changelog.

Known issues

Known issues

Hardware revisions

Revision history

Troubleshooting

Interference from relays and contactors

Relays and contactors can interfere with nearby devices. When switching loads, especially inductive loads, the contacts generate high-frequency transients with amplitudes of several kilovolts, which may couple into other circuits. Snubber networks suppress these transients, reducing interference and improving equipment stability. See Interference when switching inductive loads

Device images and drawings

WB-MRPS6 dimensions
WB-MRPS6 dimensions

CorelDRAW 2018 (font: Ubuntu): File: WB-Library.cdr.zip