Firmware is updated through the web interface; see the device manual.
Changelog
1.3.0 (06.08.2026)
- Added a Modbus bus analyzer: real-time RS-485 traffic capture in the web interface, with device-address and function-code filters, CSV export and error statistics
- Added a register-map cache: populated automatically from bus traffic and served over Modbus TCP, with value timeouts, reset and CSV/JSON export
- Added transparent RS-485 repeater mode between the device ports
- Added device-information registers at Unit ID 255, accessible over Modbus TCP
- Added TX disabling for each RS-485 port: the port physically switches to receive-only mode, allowing safe monitoring of an existing third-party bus
- Added permanent Wi-Fi disabling: the radio does not start at boot. This cannot be reversed through the API; a factory reset is required
- Added update-channel selection (stable or testing) and one-click firmware updates from the selected channel, without manually downloading a file
- Fixed firmware-file uploads from browsers on macOS
- Expanded testing significantly: over 1,800 firmware and web-interface unit tests and around 240 end-to-end tests in 50 suites, running actual firmware in an ESP32 emulator (QEMU) over HTTP, Modbus TCP and WebSocket
1.2.0 (18.05.2026)
- Updated the web-interface design
- Separated settings into Network and Serial ports pages and added a TCP gateway page
1.1.2 (08.05.2026)
- Published the firmware source code under the MIT-WB license
1.1.1 (17.04.2026)
- Added the hostname below the logo on the login screen and in the sidebar
- Added the public GET /hostname API endpoint to retrieve the hostname without authentication
1.1.0 (24.02.2026)
- Added German, Italian and Kazakh translations
1.0.7 (26.01.2026)
- Fixed firmware updates over Wi-Fi (ERRWB-MGEv30004)
- Fixed saving static IP addresses in Firefox (ERRWB-MGEv30005)
1.0.6 (29.12.2025)
- Fixed unreliable control of I/O Bus, Vout, termination and failsafe bias (ERRWB-MGEv30003)
- Renamed the Wi-Fi Station mode to Client
1.0.5 (22.12.2025)
- Disabled rebooting at startup when the supply voltage is outside the operating range (8–28 V)
1.0.4 (15.12.2025)
- Fixed incorrect reception of long RS-485 packets and incorrect operation in Modbus TCP mode (ERRWB-MGEv30002)
1.0.3 (11.12.2025)
- New devices use a stronger default Wi-Fi access-point password
1.0.2 (08.12.2025)
- Improved the web interface and added a download link for the latest firmware
1.0.1 (03.12.2025)
- Minor firmware changes
1.0.0 (11.11.2025)
- First firmware version