Wiren BoardDocumentation
Reference · English

WB-MWAC v.2 firmware changelog

revision 78918

Overview

Device firmware can be updated over Modbus; see the instructions.
This page lists changes since the beginning of 2022. Earlier changes are in Firmware Changelog.

Changelog

1.27.0 (30.09.2026) — available in testing

  • Added water-flow influence setting for anti-seize protection scheduling.
  • Added anti-seize protection statuses indicating postponement reasons.

1.26.2 (21.08.2026)

  • LED state synchronized with input level when input mode changes.
  • Fixed false front-panel button activation at firmware startup.

1.26.1 (07.08.2026)

1.26.0 (13.07.2026)

  • Added service coil register 65500 for LED testing.

1.25.1 (03.07.2026)

1.25.0 (08.06.2026)

  • Added register for audible leak-alarm duration.

1.24.1 (03.06.2026)

1.24.0 (05.05.2026)

  • Added valve anti-seize protection (WB-MWAC v.2 only)
  • Added remaining wet-cleaning time register.
  • Improved reliability during power loss.
  • Optimised filesystem operation.
  • Added FlashFS diagnostic service registers.
  • Optimized stack usage when requesting many registers.

1.23.0 (22.12.2025)

  • Added stack and RAM monitoring service registers
  • Added a service register for the last MCU reset cause
  • Added a firmware update counter service register
  • Added FlashFS diagnostic service registers
  • Added device batch-number register (WB-MWAC v.2 only)
  • Improved MCU supply voltage measurement accuracy on new devices

1.22.1 (03.10.2025)

  • Fixed configuration migration when upgrading to firmware 1.22.0 — ERRMWAC2009

1.22.0 (22.09.2025)

  • Added indication when a leak sensor has dried
  • Added an audible notification after leaving Leak mode
  • Added NO/NC leak-sensor selection
  • Added a register to restore default settings

For WB-MWAC v.2:

  • Added buzzer control through inputs, a register and Safety Mode

1.21.7 (26.05.2025)

  • Removed the ability to enable Leak mode through a Modbus register on WB-MWAC v.2 ERRMWAC2008

1.21.6 (31.03.2025)

  • Fixed relay state on first power-on of WB-MWAC v.2 ERRMWAC2007
  • Added microcontroller UID Modbus registers for WB-MWAC v.2
  • Fixed unexpected behaviour when invalid values are written to some registers ERRMODBUS003
  • Fixed loss of Modbus response under very frequent requests (observed on WB-MAP12E)

1.21.5 (13.03.2025)

  • Fixed critical firmware and bootloader errors that could prevent startup after power cycling: ERRBOOT004, ERRMWAC2006

1.21.4 (11.11.2024)

1.21.3 (14.08.2024)

For WB-MWAC:

  • Removed complementary-mode selection for noncomplementary inputs,
  • Turn all relays off on press input mode no longer disables wet-cleaning mode,
  • Status LED operation.

For WB-MWAC v.2:

  • Fixed inability to set RS-485 parity other than N ERRMWAC2003,
  • Fixed incorrect microcontroller temperature and supply-voltage measurements ERRMWAC2004,
  • Fixed ability to select nonexistent modes 0–2 in registers 9–14 ERRMWAC2005.

1.21.2 (17.05.2024)

  • Added minimum microcontroller-voltage register

For WB-MWAC:

  • Restored Alarm output switching in mapping-matrix settings

1.21.1 (03.04.2024)

  • Improved wet-cleaning mode visual indication
  • Prevented Leak mode activation while Wet cleaning mode is active
  • Prevented setting Wet cleaning timer to 0
  • Fixed persistence of Wet cleaning timer after restart
  • Fixed replies to address 0xFD packets that did not contain Fast Modbus commands ERRMODBUS001

For WB-MWAC:

  • Added sensor-state checking when leaving Wet cleaning mode
  • Fixed default input-to-output control settings

For WB-MWAC v.2:

  • Fixed persistence of Restore valve state after leak is resolved after restart
  • Significantly accelerated K1 and K2 button processing
  • Fixed counter configuration persistence after restart: Pulse weight P1/P2 and Initial counter value P1/P2
  • Added range checking for Pulse weight P1 and P2 registers

1.21.0 (25.01.2024)

Separate firmware branch for WB-MWAC and WB-MWAC v.2.

  • Fixed the Repeat after 20 minutes if input is still active function, which did not work
  • Leak sensors are now checked at startup. Previously no alarm occurred if the sensor was triggered before the device powered on
  • Added Wet cleaning mode to suspend leak-sensor response while cleaning
  • Added fail-safe alarm-output behavior settings
  • Allowed leak-sensor processing in Safety Mode
  • Added configuration-reset register
  • Added speaker-disable register
  • Added WB-MWAC v.2 support

1.20.4 (07.11.2023)

No changes for this device.

1.20.3 (11.09.2023)

No changes for this device.

1.20.1 (24.07.2023)

No changes for this device.

1.20.0 (11.05.2023)

No changes for this device.

1.19.2 (05.12.2022)

No changes for this device.

1.19.1 (16.11.2022)

No changes for this device.

1.19.0 (11.11.2022)

No changes for this device.

1.18.5 (01.07.2022)

No changes for this device.

1.18.4 (30.05.2022)

No changes for this device.

1.18.2 — 1.18.3

Experimental nonpublic versions

1.18.0 — 1.18.1

WB-MR relay branch, no changes for WB-MWAC

1.17.8 (21.04.2022)

No changes for this device.

1.17.7 (30.03.2022)

No changes for this device.

1.17.6 (30.03.2022)

No changes for this device.

1.17.5 (05.03.2022)

No changes for this device.

1.17.3 — 1.17.4

WB-MR relay branch, no changes for WB-MWAC

1.17.2 (31.01.2022)

No changes for this device.

1.17.1

WB-MR relay branch, no changes for WB-MWAC